Ames Fire & Waterworks Colt Series C200 Backflow Preventer Assemblies User Manual
Content
ames fire & waterworks Colt Series C200 Backflow Preventer Assemblies Manual
The ames fire & waterworks Colt Series C200 Backflow Preventer Assemblies are double check valve assemblies designed to protect potable water supplies from reverse flow caused by backsiphonage or backpressure. They are commonly used in fire protection systems and other applications where water may become non-potable.
The Colt C200 uses two independent Tri-Link check modules within a compact stainless steel housing. This design provides dependable flow protection while allowing the check modules to be accessed and serviced through a single sleeve opening. The removable modules are designed for maintenance without special tools, helping reduce service time during inspections or repairs.
Typical assemblies include two shutoff valves, four test cocks, and a stainless steel body with grooved or flanged connection options depending on the selected configuration. Certain versions include OS&Y gate valves and fire supervisory tamper switches for integration with fire alarm monitoring systems.
This backflow preventer is intended for qualified plumbers, fire protection contractors, water-system engineers, facility managers, and certified backflow testers. It suits commercial buildings, industrial facilities, sprinkler systems, municipal installations, and other applications requiring a double check valve assembly. Always verify the exact model, connection type, orientation, approvals, and local authority requirements before installation.
ames fire & waterworks Colt Series C200 Specifications
- Product type: Double check valve backflow preventer assembly.
- Protection method: Two independent check valves protect against backsiphonage and backpressure.
- Check design: Removable Tri-Link check modules intended for service without special tools.
- Body material: 304 stainless steel on applicable Colt C200 configurations.
- Access: Single housing sleeve access port for inspection and maintenance.
- Included service points: Four test cocks and two drip-tight shutoff valves.
- Connection options: Configuration-dependent grooved or flanged end connections.
- Maximum working pressure: Up to 175 psi on listed configurations.
- Typical temperature range: Approximately 33°F to 140°F on listed configurations.
- Installation positions: Horizontal or vertical-up installation may be permitted; follow the exact product markings and installation manual.
- Materials in the check modules: Noryl®, stainless steel, silicone, EPDM, or Buna-N components depending on the selected model.
- Standards and approvals: Applicable models may carry ASSE, CSA, UL, FM, or AWWA-related approvals. Confirm the rating plate and local code requirements before use.
How to Install and Set Up the Colt Series C200 Backflow Preventer
Step-by-step installation
- Confirm the model, nominal pipe size, connection type, pressure rating, temperature range, and required approvals.
- Shut down and isolate the water supply. Lock out connected pumps or fire-system controls when required by site procedures.
- Inspect the pipework, remove debris, and verify that the piping can support the assembly without placing strain on the valves.
- Position the assembly so the flow arrow matches the direction of water flow. Install only in an orientation approved for the exact model.
- Connect the inlet and outlet using compatible gaskets, fasteners, couplings, or flange hardware. Tighten evenly according to the applicable installation instructions.
- Install required drainage, clearance, access, and support provisions. Keep the sleeve and test cocks accessible for testing and servicing.
- Open the downstream shutoff valve slightly, then slowly open the upstream shutoff valve to fill the assembly and limit water hammer.
- Check every joint, test cock, and valve stem for leakage. Complete the required commissioning test with an authorized backflow tester.
Do not modify the check modules, bypass the assembly, or connect incompatible accessories. The C200 is not a wireless device and does not require pairing; models equipped with supervisory switches require compatible fire alarm monitoring wiring installed by qualified personnel.
Colt C200 Backflow Preventer Troubleshooting
- Water leaks at a connection: Isolate the line, depressurize it, and inspect the gasket, flange, coupling, alignment, and fastener torque. Replace damaged sealing components.
- Test failure or excessive pressure loss: Confirm that the test equipment is calibrated and connected correctly. Inspect the check modules for debris, wear, damaged seals, or incorrect installation.
- Flow will not pass: Verify that both shutoff valves are open, the flow arrow is correctly oriented, and no check module is obstructed.
- Continuous discharge from a test cock: Close the test cock only after testing is complete. If leakage continues, replace the test-cock seal or the complete serviceable component as directed by the manufacturer.
- Supervisory alarm remains active: For OS&Y versions, check that each gate valve is fully open and that the tamper switch actuator is correctly positioned. Have alarm wiring checked by a qualified technician.
- Repeated test failure: Flush the line where permitted, inspect both check modules, and schedule service by a certified backflow professional.
The manufacturer does not generally identify every service condition with universal error codes, so do not apply an unrelated code chart. Record the model and serial information, installation orientation, test readings, and observed symptoms before requesting technical support. Warranty coverage and service procedures depend on the exact product and installation; consult the current manufacturer documentation or an authorized Ames or Watts representative.
Colt Series C200 Pros and Cons
Advantages
- Serviceable modular design: The Tri-Link check modules can be removed for maintenance without special tools on applicable models.
- Durable construction: Stainless steel housing provides corrosion resistance suitable for many commercial and fire protection environments.
- Maintenance access: A single sleeve access port simplifies inspection compared with designs requiring extensive disassembly.
- Installation flexibility: Approved models support horizontal or vertical-up installation when installed according to the flow arrow and product instructions.
- System monitoring options: OS&Y configurations may include supervisory tamper switches for fire alarm integration.
- Broad application range: The assembly suits potable-water protection, sprinkler systems, commercial facilities, and industrial water installations.
Limitations
- Not suitable for every hazard: A double check assembly may not meet requirements where a reduced-pressure or detector-type assembly is mandated.
- Configuration-specific ratings: Size, connection type, orientation, approvals, dimensions, and temperature limits vary by model.
- Professional testing required: Installation and annual or jurisdictionally required testing should be performed by qualified personnel.
- Access space is essential: Poor clearance around the sleeve, test cocks, or shutoff valves can make routine service difficult.
The ames fire & waterworks Colt Series C200 Backflow Preventer Assemblies are best suited to projects requiring a compact, serviceable double check assembly with strong maintenance access. Choose another backflow protection category when local codes or the hazard level require additional protection.
Faqs
How should I install ames fire & waterworks Colt Series C200 Backflow Preventer Assemblies for the first time?
What piping and system requirements must be checked before installing a Colt Series C200 backflow preventer?
Why is the Colt Series C200 showing low flow or excessive pressure loss?
What should I do if the Colt Series C200 fails a backflow test?
How do the check valves and test cocks work in ames fire & waterworks Colt Series C200 Backflow Preventer Assemblies?
Can a Colt Series C200 be installed vertically, or must it be horizontal?
How often should I maintain and test an Ames Colt Series C200 backflow preventer?
How do I safely service the check modules in Colt Series C200 Backflow Preventer Assemblies?