Installation: Icm Controls ICM2811 Integrated Furnace Control Board Instruction Guide
Content
Overview
The ICM2811 Integrated Furnace Control Board is a microprocessor-based replacement control for compatible gas furnaces. It manages the gas valve, inducer draft motor, circulating blower, and hot surface ignitor while monitoring pressure, flame, limit, and rollout safety circuits.
This furnace control board is intended for qualified HVAC technicians performing replacement, testing, and troubleshooting. It is designed as a form, fit, and functional replacement for selected Goodman and White-Rodgers ignition control boards.
Specifications
- Model: ICM2811
- Input voltage: 18–30 VAC, 60 Hz maximum
- Hot surface ignitor relay: 6.0 amps at 120 VAC, 60 Hz resistive
- Inducer relay: 2.2 FLA to 3.5 LRA at 120 VAC
- Blower relay: 14.5 FLA to 25.0 LRA at 120 VAC for two-speed heating and cooling applications
- Gas valve relay: 1.5 amps at 25 VAC, 60 Hz, 0.6 power factor
- Operating temperature: -40° to 176°F (-40° to 80°C)
- Humidity range: 5% to 95% relative humidity, non-condensing
- Diagnostic indication: onboard LED fault display
- Twinning: compatible with another ICM2811 control board only
Replacement Applications
- Goodman: PCBBF110, PCBBF123, 0130F00005, PCBBF112, and B18099-26
- Goodman variations: PCBBF110S, PCBBF123S, 0130F00005S, PCBBF112S, and B18099-26S
- White-Rodgers: 50A55-743, 50A55-289, and 50T55-289
Detailed Description
The ICM2811 Integrated Furnace Control Board coordinates the furnace ignition sequence from the initial thermostat demand through burner operation and shutdown. It checks the combustion-air pressure switch, energizes the hot surface ignitor, controls the gas valve, verifies flame through flame rectification, and starts the circulating blower after flame has been proven.
Safety monitoring includes the high-limit circuit, rollout circuit, auxiliary limit circuit, pressure switch, flame sensor, and gas valve wiring. The control uses a 12-pin connection for major safety and low-voltage circuits and a 2-pin connection for the inducer blower and hot surface ignitor.
Connection Functions
- P1 pin 1: limit switch output
- P1 pin 2: flame-sense input
- P1 pin 3: 24 VAC input
- P1 pin 4: pressure-switch output
- P1 pin 5: rollout-switch output
- P1 pin 6: 24 VAC common
- P1 pin 7: limit-switch input
- P1 pin 8: common
- P1 pin 9: gas-valve common
- P1 pin 10: pressure-switch input
- P1 pin 11: rollout-switch input
- P1 pin 12: gas-valve output
- P2 pin 1: inducer blower
- P2 pin 2: hot surface ignitor
Safety
Turn off both electrical and gas supplies before removing or servicing the furnace control board. Failure to isolate these supplies can result in fire, explosion, electric shock, serious injury, or death.
Use electrostatic discharge precautions whenever handling the ICM2811. Disconnect furnace power, then touch a clean, unpainted metal section of the furnace chassis with your hand and tools before touching the board or wiring. Repeat the grounding procedure whenever you move around, touch an ungrounded object, or prepare to handle a replacement control.
An ESD service kit can provide additional protection. Keep the old and replacement boards separated from ungrounded objects until servicing is complete.
Before replacement, inspect the control compartment for water stains. Check nearby humidifiers, evaporator coils, and vent systems for leaks, and correct any water source before installing the new board.
Setup and Operation
Removing the Existing Control
- Set the thermostat to Off or to its lowest setting.
- Turn off electrical power to the furnace.
- Turn off the furnace gas supply.
- Remove the blower and control access doors.
- Remove the control-box cover.
- Label every wire before disconnecting it.
- Disconnect thermostat and humidifier wiring when installed.
- Disconnect line-voltage, blower, electronic air cleaner, and transformer wiring as applicable.
- Remove the wiring harness from the circuit board.
- Remove the screws or other fasteners securing the old board.
- Inspect the control and control box for evidence of water intrusion.
- Repair any leakage before continuing.
Installing the New Control
- Discharge static electricity by grounding yourself to the furnace chassis.
- Mount the ICM2811 using the original screws and fasteners where suitable.
- Reconnect line-voltage, low-voltage, accessory, thermostat, and ground wiring.
- Check all connections against the furnace wiring arrangement before restoring power.
- Restore the gas and electrical supplies.
- Verify the complete heating and cooling sequence before returning the furnace to service.
Heating Sequence
- A call for heat applies 24 VAC to terminal W.
- The inducer and optional humidifier energize, allowing the pressure safety switch to close.
- The control runs a 15-second inducer pre-purge.
- After pressure-switch verification, the hot surface ignitor receives power for a 9-second warm-up.
- The gas valve energizes and gas enters the burners.
- The ignitor lights the gas, while the flame sensor and rectification circuit check for a valid flame signal.
- The initial flame-proving period lasts 4 seconds.
- Once flame is proven, the ignitor turns off approximately 1 second later.
- The circulating blower starts after a 30-second heat blower delay.
- When the heat demand ends, the gas valve closes and the inducer runs for a fixed 15-second post-purge.
- The inducer and humidifier then turn off, followed by the heat blower after the selected off-delay.
Cooling Sequence
A cooling demand applies 24 VAC to terminal Y. The control waits 5 seconds, then energizes the cooling blower and electronic air cleaner output. When the cooling demand ends, the blower and electronic air cleaner remain active for a 45-second post-purge before turning off.
Timing Values
- Inducer pre-purge: 15 seconds
- Ignitor warm-up: 9 seconds
- Trial for ignition: 4 seconds
- Additional ignition retries: 2
- Inducer interpurge between attempts: 30 seconds
- Inducer post-purge: 15 seconds
- Heat blower on-delay: 30 seconds
- Cool blower on-delay: 5 seconds
- Cool blower off-delay: 45 seconds
- Ignition or pressure lockout: 75 minutes
- Safety recovery delay after rollout or high-limit recovery: 3 minutes
Heat Blower Off-Delay Adjustment
Move the J1 jumper to the required position to select the heating blower off-delay.
- J1 pins 1 and 2: 180 seconds
- J1 pins 2 and 3: 150 seconds
- J1 pins 3 and 4: 120 seconds
- J1 pins 4 and 5: 90 seconds
Twinning
The ICM2811 can be twinned only with another ICM2811 control board. Connect the TWIN terminals between the two furnaces, connect the common side of both 24 VAC transformers together, and bond the transformer common to earth ground. The furnace chassis must also share a ground connection.
The twinned controls are intended to operate the blowers at the same time and speed. An external AC relay is required for the heating call: its coil connects between R and W of the primary furnace, while its normally open contacts connect R and W of the secondary furnace.
LED Fault Codes
The diagnostic LED communicates operating and fault conditions through its status or flash count. Always correct the underlying furnace problem before resetting or replacing the control.
- LED on: Normal operation.
- LED off: Control failure. Check input voltage and the fuse; replace the control if the supply and fuse are correct but the fault remains.
- 1 flash: Ignition failure or soft lockout. Inspect the flame sensor, ignitor, input voltage, and transformer common-to-ground connection.
- 2 flashes: Pressure switch stuck closed. Inspect the pressure switch for contamination or failure.
- 3 flashes: Pressure switch stuck open. Check pressure tubing for obstruction, the switch, its terminals, wiring, and inducer motor.
- 4 flashes: Limit switch fault. Check for restricted airflow, blocked ductwork, a dirty filter, or a defective high-limit switch.
- 5 flashes: Flame out of sequence. Inspect the gas valve and flame sensor for intermittent operation, contamination, or failure.
- 6 flashes: Rollout switch fault. Check for a damaged heat exchanger, defective rollout switch, or broken rollout wiring.
- 7 flashes: Weak flame signal. Clean the flame sensor, verify grounding, and confirm that the sensor is properly enveloped by the flame.
- 8 flashes: Miswired gas valve. Check for shorted or incorrectly connected gas-valve wiring, damaged harness conductors, and pressure-switch operation.
- 9 flashes: Not assigned.
- 10 flashes: Hot and neutral reversed. Check polarity on the incoming supply and on both sides of the transformer.
- 11 flashes: Brownout. Measure primary and secondary transformer voltage and check for excessive transformer loading.
- 12 flashes: Twinning fault. Confirm shared transformer common, earth grounding, chassis bonding, and the wire between both TWIN terminals.
Troubleshooting
Flame Not Established
If the burner flame is not proven during the first 4-second trial, the control allows two additional ignition attempts. A 30-second inducer purge occurs between attempts. After three unsuccessful attempts, the furnace enters a 75-minute lockout before another ignition sequence can begin.
Flame Loss During Heating
When flame is lost while a heat demand remains active, the gas valve closes while the inducer and circulating blower continue operating. The control then attempts ignition again. Three unsuccessful attempts lead to a 75-minute lockout.
Flame Out of Sequence
This condition occurs when the control detects flame without a W heat signal. The inducer and blower engage if necessary and continue running while the fault remains present. Inspect the gas valve and flame-sensing circuit for unwanted gas flow or a false flame signal.
Pressure Switch Problems
If the pressure switch remains open during the initial purge, the control can extend the inducer pre-purge for up to 5 minutes. If the switch closes during that extended period, normal operation resumes. If it remains open beyond 5 minutes, the system enters a 75-minute lockout.
Limit or Rollout Recovery
After a high-limit or rollout switch re-closes, the control applies a 3-minute self-healing delay. The thermostat demand is then allowed to continue if the safety circuit remains closed. An open high-limit or rollout switch keeps the fault and lockout active.
Pros & Cons
- Pros: Integrates ignition, blower, inducer, gas-valve, flame-sensing, and safety monitoring functions in one control.
- Pros: Provides diagnostic LED codes for faster furnace troubleshooting.
- Pros: Offers selectable heating blower off-delays and compatibility with a matching ICM2811 for twinned furnace systems.
- Cons: Twinning is restricted to another ICM2811 control board and requires correct grounding and an external relay arrangement.
- Cons: Installation involves both line-voltage and gas-furnace safety circuits, so incorrect wiring can create hazardous operation.
Faqs
What safety steps should be followed before installing the ICM2811 furnace control board?
How do I replace an existing furnace control board with the ICM2811?
What does the ICM2811 LED fault code indicate when the furnace will not start?
Why does the ICM2811 keep the furnace locked out after a failed ignition?
What should be checked when the ICM2811 reports a pressure switch fault?
How can I troubleshoot a limit switch or rollout switch fault on the ICM2811?
What are the normal ICM2811 furnace heating and cooling timing delays?
Can two furnaces be twinned using the ICM2811 control board?