Installation: Alpha Technologies AlphaCap-665 Instruction Manual

Content

Overview

The AlphaCap-665 is a short-duration backup supply module designed for 48 Vdc remote power applications such as xDSL and FTTx equipment. It acts like a battery-connected hold-up device on a -48 Vdc bus, using ultra-capacitor storage and a DC-DC converter to keep critical loads running through brief interruptions.

This model is well suited to telecom sites and other remote installations that need ride-through power during transients, ground-fault resets, or brief input loss. It is also a practical option for battery-eliminated systems that still need a burst of backup power.

Specifications

  • Model: AlphaCap-665, part number 013-015-20
  • Input voltage: -48 to -56 Vdc
  • Charge current: 160 mA maximum
  • Output voltage: -46 Vdc ±3%
  • Power: 665 W nominal, 750 W maximum
  • Backup duration: 4.5 seconds at 665 W under nominal conditions
  • Backup duration: at least 3 seconds at 665 W down to -40°C
  • Backup duration: up to 30 seconds at 130 W under nominal conditions
  • Backup duration: 3.8 seconds at 750 W under normal operating conditions
  • Operating temperature: -40°C to +65°C
  • Dimensions: 43.1 mm H x 183.4 mm W x 350.5 mm D
  • Mounting: wall mount with L-shaped brackets and chassis flange mounting holes
  • Power connection: Tyco 193839-1 terminal block
  • Ground connection: two #10-32 standoffs, 5/8 inch center
  • Alarm connection: Amp 2-1445055-2 relay connector

Detailed Description

The AlphaCap-665 stores energy in an array of ultra-capacitors and releases that energy through a converter board when the main supply is interrupted. Because it parallels the load bus, it behaves similarly to a battery module from the system’s point of view, but it is intended for very short backup intervals rather than long standby runtimes.

The chassis includes two status LEDs and a dry-contact alarm relay for system monitoring. Power and alarm wiring are brought out on the side of the module, and earth grounding is provided through dedicated chassis standoffs. The unit is built for restricted-access installations where qualified personnel handle installation and service.

Safety

Installation and servicing must be done with care because hazardous voltages may be present even when AC input power is disconnected. The module is intended for restricted-access locations and should be handled only by qualified personnel.

  • Remove metal jewelry before working on live equipment.
  • Wear safety glasses with side shields and use insulated tools approved for electrical work.
  • Assume conductors are energized until verified with a voltmeter.
  • Do not work alone under hazardous conditions.
  • Disconnect and lock out utility power before installation or removal procedures.
  • Keep liquids and wet clothing away from internal components.
  • Battery work requires eye protection, rubber gloves, and protective clothing.
  • Avoid sparks, smoking, and open flames near charging batteries.
  • Use proper recycling methods for battery disposal.

The enclosure can contain hot surfaces, sharp metal edges, and moving fans, so hands and tools should be kept clear during operation and maintenance.

Setup and Operation

Before installation, inspect the shipment for container damage and check the module for visible or hidden damage. Keep the original packaging if the unit may need to be returned for service.

The AlphaCap-665 is mounted to a clean, dry wall location using the chassis mounting holes and L-shaped wall brackets. Wiring is accessed from the side of the unit, with separate provisions for power, ground, and alarm wiring.

Power and Connections

  • Connect -48 and +RTN using the specified 2-position Tyco terminal block and compatible mating connector.
  • Use #12 to #18 AWG TEW 90 wire or equivalent for the power connection.
  • Connect chassis earth ground to the provided #10-32 studs.
  • Wire the alarm relay through the Amp Mate-N-Lok alarm connector.

The charge circuit is limited to 160 mA, which helps minimize the power drawn from the source during recharge. The unit returns to full capacity in about 30 minutes after discharge, regardless of how deeply it was used.

Status Indications

  • Solid green: normal operation
  • Flashing green: charging
  • Alternating green and amber: backup mode
  • Alternating green and red: overcharge or charging circuit failure
  • Solid red or no light: module failure

The dry-contact alarm relay is normally closed in alarm logic terms and changes state when a fault is detected. It can signal capacitor discharge, low input shutdown, overcharge shutdown, over-temperature shutdown, internal reference errors, or a blown fuse.

Temperature Performance

The normal operating range is -40°C to +65°C. A shutdown occurs at +65°C, and normal operation resumes after the temperature drops to +60°C. The 5°C hysteresis helps prevent rapid cycling near the trip point.

Backup duration drops as temperature rises, and long-term capacitor life also decreases in hotter environments. For example, at a 350 W load, holdup after 10 years is longer at 25°C than at 45°C or 55°C.

Cleaning and Maintenance

Routine maintenance is limited, but annual inspection is recommended to keep the system performing reliably. Check connections, verify alarm and control settings, and re-torque hardware if needed.

Work inside the unit only when necessary and only by qualified service personnel. The cover should remain closed because there are no user-serviceable parts inside. Static-sensitive components should be handled with proper grounding precautions.

Troubleshooting

Status LEDs and relay behavior provide the main clues for diagnosing AlphaCap-665 faults. A solid red LED or no LED indication points to a module failure, while alternating green and red indicates an overcharge condition or charging circuit problem.

  • Backup mode with alarm output active may indicate the module is supplying hold-up power.
  • No backup when needed may indicate a fully discharged capacitor state or low-voltage input shutdown.
  • Persistent alarm output can also be caused by over-temperature shutdown, internal reference error, or a blown fuse.

Warranty

The standard warranty covers repair, replacement, or credit at the manufacturer’s discretion for covered equipment returned during the warranty period. It does not cover losses such as lost profits, installation or removal costs, consequential damages, or failures caused by outside factors such as environmental conditions, water damage, or power surges.

Shipping and handling are the customer’s responsibility when returning a unit, although return shipping for repaired or replacement products is covered when the item is approved under warranty.

Pros & Cons

  • Pros: Compact short-duration backup for 48 Vdc telecom loads; fast recharge; simple single-bus wiring; clear LED and relay status; wide temperature range.
  • Cons: Designed for brief hold-up rather than long runtime; performance drops at higher temperatures; requires qualified installation and careful electrical safety practices.

PDF

Faqs

How do I install the AlphaCap-665 safely in a 48 Vdc power system?

The AlphaCap-665 is meant to be installed by qualified personnel in a clean, dry, restricted-access location. It connects in parallel to a -48 Vdc bus, similar to a battery, using the single power input/output connection. Before wiring, make sure utility power is disconnected and locked out, and treat every conductor as energized until verified with a voltmeter. A licensed electrician is required for permanently wired equipment, and insulated tools, safety glasses, and proper grounding practices are essential.

What does the AlphaCap-665 status LED mean during normal operation and backup?

The bi-color status LED gives a quick snapshot of module health. Solid green means the unit is OK, while flashing green means it is charging. Alternating green and amber indicates the module is providing backup power. Alternating green and red points to an over-charging condition or a charging circuit failure. Solid red or no light indicates a module failure, so the unit should be checked along with the alarm relay and input conditions.

How long can the AlphaCap-665 keep equipment running during a power interruption?

Backup duration depends on load, temperature, and operating conditions. Under nominal conditions, the AlphaCap-665 can supply 665 W for about 4.5 seconds, and it can support up to 750 W for about 3.8 seconds. At lower load, it can hold up longer, with a maximum of around 30 seconds at 130 W. The manual also notes reduced holdup time as temperature rises, so real-world performance may vary.

What input voltage and charging behavior should I expect from the AlphaCap-665?

The unit is designed for a -48 to -56 Vdc input range and uses a built-in charge limit of 160 mA maximum. That low charging current helps minimize the extra power drawn from the remote load. A full recharge is expected within about 30 minutes, regardless of how deeply the module was discharged. This makes it well suited for systems that need short-duration holdup without placing a heavy burden on the power bus.

What should I know about the AlphaCap-665 alarm relay connection?

The AlphaCap-665 includes a dry-contact alarm relay with a normally closed configuration. During normal operation, the relay is energized and open; when an alarm occurs, it de-energizes and closes. The relay can signal several fault conditions, including full discharge, low-voltage input shutdown, overcharge shutdown, over-temperature shutdown, internal voltage reference error, and a blown fuse. The relay is rated for a maximum load of 2A / 60W.

What temperature range does the AlphaCap-665 support, and when does it shut down?

The operating range is -40°C to +65°C, but performance changes as temperature rises. High-temperature shutdown occurs at +65°C, and normal holdup and charging resume when the temperature drops to +60°C. The manual also states that holdup duration decreases at higher temperatures, and capacitor life is reduced over time in hot environments. For best results, keep the unit in a location where ambient heat is controlled.

What wiring and connector details matter during AlphaCap-665 installation?

The power connection uses a 2-position Tyco terminal block and requires -48 and +RTN wiring with #12-18 AWG TEW 90 wire or equivalent. The unit also includes earth-ground standoffs on the chassis for proper grounding. Alarm wiring uses an Amp Mate-N-Lok connection, with pin 1 as Common and pin 2 as NC. Making the correct connector and polarity match is important to avoid startup issues or alarm faults.

What basic maintenance checks should be done on the AlphaCap-665?

The manual recommends routine checks at least once a year, even though the system needs very little maintenance. Inspect all connections, re-torque them if necessary, and verify alarm and control settings. Maintenance should only be done by qualified service personnel, and care is required because hazardous voltages can remain present even when AC input is disconnected. The cover should not be opened, since there are no user-serviceable parts inside.

More alpha technologies manuals